Modbus Installation | 30
Variable
Name
Description
Addr
Type
Format
Range
Unit
R/W
Additional Details
Fault
Read fault status
30301
Input
Register
Binary
0,1
-
Read
0 = No Fault
1 = Fault Detected
Service
Read service
warning status
30300
Input
Register
Binary
0,1
-
Read
0 = No Service
Warning
1 = Service Required
Status
Read
humidification
status
30302
Input
Register
Binary
0,1
-
Read
0 = Idle / Standby
1 = Active /
Humidifying
Connection
Read connection
status
40267
Input
Register
Binary
0,1
-
Read
0 = Communication
Error
1 = Normal
Communication
HourOpt
Read operational
hours of unit
30350
Input
Register
Analog
0 -
Infinity
hrs
Read
Displays hours of
operation.
KeepWarm
Read keepwarm
option status
(enable/disable at
humidifier)
30356
Input
Register
Analog
0,1
-
Read
Bit0 - KEEPWARM
0 = Disabled
1 = Enabled
3DayDrain
Read 3 day drain
option status
(enable/disable at
humidifier)
30356
Input
Register
Analog
0,1
-
Read
Bit1 - 3 DAY DRAIN
0 = Disabled
1 = Enabled
SysDemand
Read system
output / demand
30347
Input
Register
Analog
0-100
%
Read
Displays output as
percentage of
capacity
ServHours
Read hours before
next service
30352
Input
Register
Analog
500-0
hrs
Read
Displays hours
remaining until next
service.
SecurityLoop
Displays status of
security loop.
30364
Input
Register
Analog
0,1
-
Read
Displays the status of
the security loop on
terminals 1 and 2.
Loop must be
"closed" for humidifier
to operate.
0 = Open
1 = Closed