Modbus Installation | 34
Variable
Name
Description
Addr
Type
Format
Range
Unit
R/W
Additional Details
1 = Service
Required
Status
Read humidification status
30302
Input
Register
Binary
0,1
-
Read
0 = Idle / Standby
1 = Active /
Humidifying
Connecti
on
Read connection status
40267
Input
Register
Binary
0,1
-
Read
0 = Communication
Error
1 = Normal
Communication
HourOpt
Read operational hours of unit
30350
Input
Register
Analog
0 -
Infi
nity
hrs
Read
Displays hours of
operation.
KeepWar
m
Read keepwarm option status
(enable/disable at humidifier)
30356
Input
Register
Analog
0,1
-
Read
Bit0 - KEEPWARM
0 = Disabled
1 = Enabled
3DayDrai
n
Read 3 day drain option status
(enable/disable at humidifier)
30356
Input
Register
Analog
0,1
-
Read
Bit1 - 3 DAY DRAIN
0 = Disabled
1 = Enabled
SysDema
nd
Read system output / demand
30347
Input
Register
Analog
0-
100
%
Read
Displays output as
percentage of
capacity
ServHour
s
Read hours before next
service
30352
Input
Register
Analog
500
-0
hrs
Read
Displays hours
remaining until next
service.
SecurityL
oop
Displays status of security
loop.
30364
Input
Register
Analog
0,1
-
Read
Displays the status
of the security loop
on terminals 1 and
2. Loop must be
"closed" for
humidifier to
operate.
0 = Open
1 = Closed