INSTRUCTION GUIDE
SC-Series Refrigerant
Leak Detector
026-4426 R2
©2024 Copeland LP.
Wiring and Controller Setup
General
The SC refrigerant leak sensor is a series of transmitters for measuring concentration of
different gases. The transmitter is available in the Standard Room Type. The sensor
heads are semi-conductive, which provides a long lifetime and stability, but with limited
selectivity.
The transmitter gives a non-linear output signal (4 to 20mA or 0 to 10V DC) proportional
to the gas concentration. For long wiring installations, it is recommended to use the
current output signal to minimize the risk of interference. Output signal mode is set by
jumper (JP1).
*
Technical Data
*
Specifications subject to change
Table 1: Sensor Technical Specs
Sensor Type Semiconductor
Response Time (T90) < 10 seconds
Operating Temperature -40°F to 122°F (-40°C to 50°C)
Operating Humidity 10 to 90% Rh (non condensing)
Dimensions 130x82x56 mm
Housing Polycarbonate / ABS
Output Signal 4 to 20mA (max 500 ohm) or 0 to 10V DC
Calibration Zero/span ≥ once per year
Lifetime Sensor
> 5 years (replacement recommended every 5
th
year or when unit cannot be calibrated)
Power Supply 12 to 30V DC (Recommended 24VDC @ 15W,120V, DIN Rail mount P/N 250-2541)
Cable gland 1 x M16