SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL 4KW
Input Voltage Waveform Sinusoidal (utility or generator)
Nominal Input Voltage 230Vac
Low Loss Voltage
170Vac±7V (UPS);
90Vac±7V (Appliances)
Low Loss Return Voltage
180Vac±7V (UPS);
100Vac±7V (Appliances)
High Loss Voltage 280Vac±7V
High Loss Return Voltage 270Vac±7V
Max AC Input Voltage 300Vac
Nominal Input Frequency 50Hz / 60Hz (Auto detection)
Low Loss Frequency 40±1Hz
Low Loss Return Frequency 42±1Hz
High Loss Frequency 65±1Hz
High Loss Return Frequency 63±1Hz
Output Short Circuit Protection Circuit Breaker
Efficiency (Line Mode) >95% ( Rated R load, battery full charged )
Transfer Time
10ms typical (UPS);
20ms typical (Appliances)
Output power derating:
When AC input voltage drops to 170V,
the output power will be derated.
Input Voltage
Output P
ower
Rated Power
50% Power
90V 170V
280V