Operation
7
-
4
7. Using the wrenches supplied in the tool kit, disconnect the high and low pressure flex
lines from the helium compressor package by turning the Aeroquips counterclockwise
with one wrench while holding the other wrench to prevent the flex line from twisting.
See Figure 7-1.
Figure 7-1: Disconnecting flex lines from a helium compressor package
IMPORTANT
When connecting or disconnecting Aeroquips, Cryomech, Inc recommends using a small amount of
dry Teflon spray lubricant. Follow the manufacturer’s instructions for its use. Do not spray lubricant
onto sealing surfaces of the Aeroquips, Hand tighten Aeroquips then spray small amount lubricant on
the threads of the male Aeroquip. See Figure 7-2.
Figure 7-2: Dry Teflon spray lubricant guidelines
Hold this wrench
Turn this wrench