6. Constant tables
■
Constant
NO
Name Description
Setting
value
Factory
setting
Change
during
operation
Com.
add.
Page
CE-60
PID offset
adjust
Adjust offset of PID output ±100 0 Yes 288 P65
CE-61
PID output
delay time
Set low-pass filter time of PID output 010 0 Yes 289 P65
CE-62
PID output
characteristics
selecting
PID output forward/ reverse characteristics
0: Normal
1: Inverting
01 0 No 290 P65
CE-63
PID output gain Set amplify magnification of PID output 025 1 No 291 P65
CE-64
PID output
reverse
selecting
0: Limit output is 0 when PID output is negative
1: PID output is negative when reverse, output is 0
when set Cd27= 1
01 0 No 292 P65
CE-65
PID command
acceleration/
deceleration
time
Set PID command acceleration/ deceleration time,
setting value is the time that accelerates from 0 to
100%
No 293 P66
CE-66
Position of P
controller
selecting
0: P control independence
1: Enter I、D controller after error passed by P
controller
01 0 No 294 P66
CE-67
PID output
delay position
selecting
0: PID output delay
1: D control output delay
01 0 No 295 P66
CE-68
Select I control
reset
0: Clear I control integral value when stop operation
1: Use terminal to eliminate integral
01 0 No 296 P66
CE-69 Reserved
CE-70
Serial
communication
position
Set address of inverter 0240 240 Yes 209
P73
CE-71
Serial
communication
speed
0: 1200 bps 1: 2400 bps 2: 4800 bps
3: 9600 bps
03 3 No 210
P73
CE-72
Serial
communication
feedback time
Set the time of inverter from received data to start
replying data
265 2mS No 211
P74
CE-73 Reserved
CE-74
Parity bit
Check
0: Invalid 1: Odd Parity bit 2: Even Parity bit 02 0 No 213 P74
CE-75
LCD
permutation
selecting
Select LCD display method 0: 2 combinations
1: 4 combinations
2: 8 combinations
02 0 No X
P92
CE-76
LCD group
selecting
Set LCD display contents function 03 0 No X P92
CE
77-80
Reserved
CE-81
IN1 transform
magnification
value
Screen indicates kg value
0.0
50.0
10.0 No X
P93