◆Stop method selecting
Description:
Cd44= 0: Deceleration stop
Set the motor to decelerate to stop according to selecting time after set Cd44= 0, (factory setting: Cd09
deceleration time 1). If DC braking were set when stop, DC braking is proceed when output frequency is
lower than Cd23
Cd44=1: coast stop
If the stop command is input when set Cd44=1, the inverter output voltage is interrupted, the motor coasts to
stop at inertia the load.
Cd44=2: Coast stop, but restart after the deceleration time is reached.
If the stop command is input when Cd44=2, the inverter output is interrupted to coast the motor to stop. the
motor coasts to stop at inertia the load. Run commands are ignored until the time has elapsed. Set timer time
by Cd10(acceleration time 2).
8. Constant setting by function
Constant
No.
Constant name Settable range Factory setting
Change during
operation
Cd44 Stop method selecting 0󲕏2 0 X
Run command
Output frquency
ON
OFF
DC injection brake
Decelerates to stop
at deceleration time
Run command
Decelerates to stop
at deceleration time
ON
OFF
Run command
Decelerates to stop
at deceleration time
ON
OFF
ON
OFF
ON
Lgnore run command
According to select frequency when
decelerated time and stop to proceed time
DC injection brake time when stopping
CD26