27
6. Constant tables
■
Constant
NO
Name Description
Setting
value
Factory
setting
Change
during
operation
Com.
add.
Page
Cd-16 Start frequency Set motor start frequency 0.560.0
1.5
HZ
No 144 P47
Cd-17
Upper limiter of
frequency
Set upper limiter of frequency command
10.00
400.00
60.00
HZ
No 145 P60
Cd-18
Lower limiter of
frequency
Set lower limiter of frequency command
0.0
100.00
0HZ No 146 P60
Cd-19
Acce./ dece. of
Joging
The time needed for set frequency
from 0 HZ to 5 Hz
0.0
6000.0
1.0S No 147 P52
Cd-20
Jump frequency 1
0400.00 0HZ No 148 P47
Cd-21
Jump frequency 2
Set the middle value of jump frequency, set 0 is
invalid.
0400.00 0HZ No 149 P47
Cd-22
Jump frequency
width
Set jump frequency width 020.0 0HZ No 150 P47
Cd-23
DC break
frequency
Start the DC break frequency as HZ when decelerate
to stop. Start frequency (Cd16) when Cd23< start the
DC break frequency (Cd16).
0.020.0 1HZ No 512 P48
Cd-24
DC break
current
Set the inverter rated current as a percentage. Set the
DC break time when start. The setting value is 0.00S,
and the DC break is invalid when start.
0100 50% No 513 P48
Cd-25
DC break time
when start
The setting value is 0.00S, and the DC break is
invalid when start.
010.00 0.00S No 514 P48
Cd-26
DC break time
when stop
The setting value is 0.00S, and the DC break is
invalid when stop.
010.00 0.00S No 515 P48
Cd-27
Prohibited revers
selectin
0: Reverse
1: Prohibited reverse
01 0.00 No 155 P45
Cd-28
Speed search
function selecting
0: Invalid
1: MCK feedback
2: Detected current +MCK feedback
3: MCK disconnection start + coast start
03 0.00 No 156 P83
Cd-29 TIME
For replay,DOfunction selecting when operation i
timing
060000 5S Yes 157 P55
Cd-30
Analog input
filter time
Set filtered of analog input terminal time, noise wil
be filtered, but input reaction will become slow.
11000 5 Yes 517 P49
Cd-31 IN1 input gain
Set percentage 100% when input 10V to correspond
selecting function 100%
0100.0
100.0
%
Yes 518 P49