35
6. Constant tables
■
Constant
NO
Name Description
Setting
value
Factory
setting
Change
during
operation
Com.
add.
Page
CE-32
12
th
step time
setting
Multi-step function control 12
th
step time setting 0255 0 No 260 P68
CE-33
13
th
step time
setting
Multi-step function control 13
th
step time setting 0255 0 No 261 P68
CE-34
14
th
step time
setting
Multi-step function control 14
th
step time setting 0255 0 No 262 P68
CE-35
15
th
step time
setting
Multi-step function control 15
th
step time setting 0255 0 No 263 P68
CE-36
16
th
step time
setting
Multi-step function control 16
th
step time setting 0255 0 No 264 P68
CE
37-46
Reserved
CE-47
Multi-step
function mode
(continuous
operation)
selecting
Select liner or gradually operation method 06 0 No 275 P69
CE-48
Multi-step
function mode
reset
Reset procedure and time to zero 01 0 Yes 276 P69
CE
49-53
Reserved
CE-54
Select PID
control
0: invalid
1: PID output is inverter output, D control error
2: PID output is inverter output, D control feedback
3: PID output is adjustment of inverter output, D
control error
4: PID output is adjustment of inverter output, D
control feedback
04 0 No 282 P64
CE-55
Proportional
control ( P )
Set ratio gain of P control 025 1.0 Yes 283 P65
CE-56
Integral time
( I )
Set integral time of I control 0360 1.0 Yes 284 P65
CE-57
Maximum
value of
Integral control
( I )
Set maximum value of integral time, set maximum
frequency as 100%
0100 100 Yes 285 P65
CE-58
Derivative time
(D)
Set derivative time of D control 010 0 Yes 286 P65
CE-59
Maximum
value of PID
output
Set limit value of PID output, set maximum
frequency as 100%
0100 100 Yes 287 P65