Function Code Table
Code
No.
Function Detail of Data Initial factory
setting
MODBUS
Address
Cd79 Auto record when 0: de-active 1
power off
Cd80 Modbus protocol
data frame and
Communications
mode setting
1: active
0: De-active
1: Active with RTU mode, only for
monitoring.(8,n,1)
2: Active with RTU mode, change
general parameter.(8,n,1)
3: Active with RTU mode, change of
general parameter. Operational
command by remote control.(8,n,1)
4: Active with ASCII mode, only for
monitoring.(7,e,1)
5: Active with ASCII mode, change
general parameter.(7,e,1)
6: Active with ASCII mode, change of
general parameter. Operational
command by remote control.(7,e,1)
3 208
Cd81 RS485
Communication ID
Setting
1240
1 209
Cd82 RS485 Baud rate 0:2400 bps
1:4800 bps
2:9600 bps
3:19200 bps
Series
2 210
211
Cd83 communication
response time.
015
0
Cd84 Series
Communication
broadcasting
function selection
Cd85 Reserved
0: Active both group and global
broadcasting
1: Active only group broadcasting.
2: Active only global broadcasting
3: De-active both group and global
broadcasting.
0 212
Cd86 RS485 interface 0: Use A+, A- port as RS422/RS485 0
selection
Cd87 Reserved
with modbus protocol
1: Use A+, A- port be de-active
2: only use remote key pad