Adjust and Function Specification
§Cd59 External terminal 4/6,3/5 function selection (Setting range 0-7)
This function is to select setting common terminal 3,4,5 and 6.
CD59 Common input terminal setting
DI4 DI6 DI3 DI5
0
JOG MBS 3DF 2DF
1
JOG/
Yards counter
RST 3DF/
Down speed %
2DF/
UP speed %
2
5DF MBS 3DF 2DF
3
5DF RST 3DF 2DF
4
JOG MBS DOWN UP
5
JOG RST DOWN UP
6
5DF MBS DOWN UP
7
5DF RST DOWN UP
Terminal specification:
JOG: Jogging operation, accommodating with Cd15.
5DF: Multi-speed, accommodating with Cd4041, 42, 43 speed setting.
MBS: Free run stop, operates both panel key and external signal.
RST: Reset, operates both panel key and external signal
2DF: Second term operation, accommodating with Cd12 speed setting.
3DF: Third term operation, accommodating with Cd13 speed setting.
UP: Using external terminal control on frequency increasing. Max. frequency is
setting of Cd00
DOWN: Using external terminal control on frequency decreasing. Min. frequency is
setting of Cd16
Note: when use multi-steps function, and Cd59=1, functions of external terminal 3,4,5
are listed as below
Terminal 3: “Down Speed %”, means the speed will be decreased, according to
function CE37~CE45.
Terminal 4: Yards counter
Terminal 5: “Up Speed %”, means the speed will be decreased, according to
function CE37~CE45.