3. Outlet Management
Intelligent PDU Web Interface
3. Outlet Management
The following provides the outlet configurations to meet different application scenarios.
3.1 Remote Outlet On/Off/Reboot
Users can turn on, turn off, or reboot individual outlet. See PDU Tab > Outlet Action >
Control. (For Switched Metered by Outlet Series and Switched Series only.)
PDU Tab > Outlet Action > Control
Item Definition
HOST/GUEST#
Select the role of PDU (HOST or GUEST#) if PDUs are daisy
chained. Up to 3 GUEST PDUs can connect to 1 HOST PDU.
Control Action
Turn On Selected outlets will be immediately turned on.
Turn On + Delay
Selected outlets will be turned on according to each
outlet’s Power On Delay in
PDU Tab > Manager > Outlet
.
Turn Off Selected outlets will be immediately turned off.
Turn Off + Delay
S
elected outlets will be turned off according to each
outlet’s Power Off Delay in
PDU Tab > Manager > Outlet
.
This action could signal a computer to shut down, if
PowerPanel® Business Edition Client software is installed on
it.