Overview
The CyberPower Relay Control Card (
solution for UPS status monitoring and local device control
relays. In addition, the
UPS shutdown
CyberPower Online UPS
Notice: The UPS can remain on when installing the
1. Remove the
two retaining screws of the expansion port cover then
remove the cover.
2.
3. Re-
install and tighten the retaining screws.
Electrical
Power Dissipation
Physical
Weight
Environmental
Operating Humidity
The CyberPower Relay Control Card (
RELAYIO600
solution for UPS status monitoring and local device control
provides
1 input contact to perform
.
This card is compatible with
s with an
Notice: The UPS can remain on when installing the
two retaining screws of the expansion port cover then
RELAYIO600 card
install and tighten the retaining screws.
RELAYIO600
7.5 -
43 x 67 x 1
1.7 x 2.64 x
0 - 40
32 - 104
) offers users a
solution for UPS status monitoring and local device control
via 5 output
1 input contact to perform
This card is compatible with
.
two retaining screws of the expansion port cover then
.7 mm
in
Internal Circuit-DB9
I/O Pinout Definition-DB9
PIN
Assignment
Function I/O Jumper
PIN 1 UPS FAIL O/P JP1
PIN 2 SUMMARY ALARM O/P JP2
PIN 3 GND (Common for PIN 4)
Power GND N/A
PIN 4 REMOTE SHUTDOWN Power + Vcc
N/A
PIN 5 COMMON (For Relays) O/P N/A
PIN 6 BYPASS / UPS OFF O/P N/A
PIN 7 BATTERY LOW O/P JP3
PIN 8 UPS ON O/P N/A
PIN 9 POWER FAIL O/P JP4
Note1: Relay contact PIN 1/2/7/9 can be configured as Normally Open (NO)
or Normally Closed (NC).
Note2: Please see the Function Description section for details on jumper
position settings.
Internal Circuit-Terminal Block
I/O Pinout Definition-Terminal Block
Function I/O Jumper
T1 REMOTE SHUTDOWN Power + Vcc
N/A
T2 GND (Common for PIN 4)
Power GND N/A
T3 SUMMARY ALARM O/P JP2
T4 BYPASS / UPS OFF O/P N/A
T5 BATTERY LOW O/P JP3
T6 POWER FAIL O/P JP4
T7 UPS ON O/P N/A
T8 UPS FAIL O/P JP1
T9 COMMON (For Relays) O/P N/A
T10 COMMON (For Relays) O/P N/A
Note1: Relay contact T3/5/6/8 can be configured as Normally Open (NO) or
Normally Closed (NC).
Note2: Please see the Function Description section for details on jumper
position settings.