activates the help outputs for the area to which the setting is assigned.
When it is in an alarm state, the LCD display shows MEDICAL ALARM.
Key: The key type zone is used as an auxiliary command to arm/disarm
one or more areas. For details, see Key Type Zone.
Each wired zone can be connected according to seven different criteria:
N.O., N.C: Select N.O or N.C depends on the output type of detectors.
For example, if the output of detector is set to N.O., then you should
select N.O.
1EOL, 2EOL, 3EOL: For definition, see "1.3 Terms and Definitions." For
wiring, see Figure 1-6.
INERTIAL: If INERTIAL is selected, the level of sensitivity must be set.
The range is 20ms–5020ms, and the detector type can be N.O. or N.C.
IMPULSE: If IMPULSE is selected, the times of impulse triggered and
impulse time must be set. The times range is 2–15. For example, if you
set range to be 5, the triggered time is set to be 000.01, this setting
means the alarm is triggered for 5 times within 1 second. The detector
type can be N.O. or N.C.
Each wired zone can be assigned to one or more areas (1 to 8). The areas
can be assigned in individual or combined mode, In the case of multiple
areas, the zone is linked to them in OR mode or arms when one of them is
armed and disarms when all of them are disarmed.
To assign or remove Areas from the Keypad, press the corresponding key
(1 to 8) and then press . The number of the assigned Area appears on
the programming line to confirm that the selection was successful. The
number of the assigned Area disappears from the programming line to
confirm that the deselection was successful.
For more details, see "1.27 AREAS."
Each wired zone can be programmed so that it is excludable by the User or
not.
NO: Establishes that the wired zone cannot be bypass by the User.
TEMPORARY: Establishes that the wired zone can be bypass but,
when the area to which it belongs is disarmed, it is automatically
re-included.
PERMANENT: Establishes that the wired zone can be bypass and
does not re-arm automatically. Re-inclusion must be performed
manually as described in the ZOME MANAGER of User Menu.
Each individual wired zone can be assigned for Partition 1 type arming. If
this option is set to YES, the wired zone will be involved in the Partition 1
arming of the areas which it belongs to.
Each individual wired zone can be assigned for Partition 2 type arming. If
this option is set to YES, the wired zone will be involved in the Partition 1
arming of the areas which it belongs to.
Each individual wired zone can be programmed to be automatically
excluded or not when the Area is armed if the wired zone is not ready (for
example, an open window).