EasyManuals Logo

Daikin 5MXM-M User Manual

Daikin 5MXM-M
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
ESIE16-02B | Part 2. Troubleshooting 2.4. Component checklist
Page 48 4/04/17 | Version 1.1
RA R32 Split & multi split M-Series
7. Megger the compressor using 500 or 1000 VDC, the insulation must be higher than 3 M.
8. Replace the compressor if the windings and/or insulation measurements fail (refer to "Replacing compressor" on page 76).
9. Run the compressor and measure the current in each phase; the current for each phase should be identical (refer to "Product
specific information" on page 111). In that case it can be decided to preventively replace the compressor (refer to "Replacing
compressor" on page 76).

Table of Contents

Other manuals for Daikin 5MXM-M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 5MXM-M and is the answer not in the manual?

Daikin 5MXM-M Specifications

General IconGeneral
BrandDaikin
Model5MXM-M
CategoryAir Conditioner
LanguageEnglish

Related product manuals