10 | Configuration
Installer reference guide
189
EPRA08~12EAV3+W1 + ETVH12SU18+23EA6V
Daikin Altherma 3 H MT F
4P644482-1 – 2021.03
In case of Schedule only or Schedule + reheat domestic hot water
preparation, the storage comfort temperature is weather dependent (according to
the weather dependent curve), the storage economic and reheat temperature are
NOT weather dependent.
In case of Reheat only domestic hot water preparation, the desired tank
temperature is weather dependent (according to the weather dependent curve).
During weather dependent operation, the end-user cannot adjust the desired tank
temperature on the user interface. Also see "10.4 Weather-dependent
curve"[4149].
# Code Description
[5.C] [0-0E]
[0-0D]
[0-0C]
[0-0B]
WD curve:
T
DHW
T
a
[0-0C]
[0-0B]
[0-0E] [0-0D]
▪ T
DHW
: The desired tank temperature.
▪ T
a
: The (averaged) outdoor ambient
temperature
▪ [0-0E]: low outdoor ambient temperature: –
40°C~5°C
▪ [0-0D]: high outdoor ambient temperature:
10°C~25°C
▪ [0-0C]: desired tank temperature when the
outdoor temperature equals or drops below
the low ambient temperature: 45°C~[6‑0E]°C
▪ [0-0B]: desired tank temperature when the
outdoor temperature equals or rises above the
high ambient temperature: 35°C~[6‑0E]°C
Margin
In domestic hot water operation, the following hysteresis value can be set for the
heat pump operation:
# Code Description
[5.D] [6-01] The temperature difference determining the heat
pump OFF temperature.
Range: 0°C~10°C
Example: setpoint (T
U
)>maximum heat pump temperature–[6‑01] (T
HP MAX
–[6‑01])