6 | Application guidelines
Installer reference guide
48
EPRA08~12EAV3+W1 + ETBH/X12EF6V+9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
INFORMATION
▪ During heating operation of the heatpump, the heatpump operates to achieve
the desired temperature set via the user interface. When weather-dependent
operation is active, the water temperature is determined automatically
depending on the outdoor temperature.
▪ During heating operation of the auxiliary boiler, the auxiliary boiler operates to
achieve the desired water temperature set via the auxiliary boiler controller.
Setup
▪ Integrate the auxiliary boiler as follows:
A Main leaving water temperature zone
B One single room
a Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
b Non-return valve (field supply)
c Shut-off valve (field supply)
d Auxiliary boiler (field supply)
e Aquastat valve (field supply)
NOTICE
▪ Make sure the auxiliary boiler and its integration in the system complies with
applicable legislation.
▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler
system.
▪ Make sure the return water to the heatpump does NOT exceed 60°C. To do so:
- Set the desired water temperature via the auxiliary boiler controller to
maximum 60°C.
- Install an aquastat valve in the return water flow of the heat pump. Set the
aquastat valve to close above 60°C and to open below 60°C.
▪ Install non-return valves.
▪ An expansion vessel is already pre-mounted in the indoor unit. But for bivalent
operation, also make sure that there is an expansion vessel in the auxiliary boiler
loop. Otherwise when bivalent operation is running and if the Aquastat valve
would close, there would be no expansion vessel in the water circuit anymore.
▪ Install the digital I/O PCB (option EKRP1HBAA).