10 | Configuration
Installer reference guide
161
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
# Code Description
[5.6] [6-0D] Heat up mode:
▪ 0: Reheat only: Only reheat operation is
allowed.
▪ 1: Schedule + reheat: The domestic hot
water tank is heated according to a schedule
and between the scheduled heat up cycles,
reheat operation is allowed.
▪ 2: Schedule only: The domestic hot water
tank can ONLY be heated according to a
schedule.
See the operation manual for more details.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
# Code Description
[5.7.1] [2‑01] Activation:
▪ 0: No
▪ 1: Yes
[5.7.2] [2‑00] Operation day:
▪ 0: Every day
▪ 1: Monday
▪ 2: Tuesday
▪ 3: Wednesday
▪ 4: Thursday
▪ 5: Friday
▪ 6: Saturday
▪ 7: Sunday
[5.7.3] [2‑02] Start time
[5.7.4] [2‑03] Tank setpoint:
60°C
[5.7.5] [2‑04] Duration:
40~60minutes