EasyManua.ls Logo

Daikin Altherma EAVX-D9WG - Main Zone

Daikin Altherma EAVX-D9WG
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Configuration
Installer reference guide
47
EPGA11~16DAV3 + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556070-1 – 2019.02
NOTICE
When adjusting the room temperature ranges, all desired
room temperatures are also adjusted to guarantee they are
between the limits.
# Code Description
[1.5.1] [3-07] Heating minimum
[1.5.2] [3-06] Heating maximum
[1.5.3] [3-09] Cooling minimum
[1.5.4] [3-08] Cooling maximum
Room sensor offset
ONLY applicable in case of room thermostat control. You can
calibrate the (external) room temperature sensor. It is possible to
give an offset to the room thermistor value measured by the user
interface used as room thermostat or by the external room sensor.
The settings can be used to compensate for situations where the
user interface used as room thermostat or the external room sensor
CANNOT be installed on the ideal installation location (see
"5.7Setting up an external temperature sensor"on page21).
# Code Description
[1.6] [2-0A] Room sensor offset (user interface used
as room thermostat): Offset on the actual
room temperature measured on the user
interface used as room thermostat.
–5°C~5°C, step 0.5°C
[1.7] [2-09] Room sensor offset (external room
sensor option): ONLY applicable if the
external room sensor option is installed
and configured.
–5°C~5°C, step 0.5°C
8.4.3 Main zone
Setpoint screen
You can set the leaving water temperature for the main zone using
the setpoint screen. For more information about how to do this, see
"8.3.5Setpoint screen"on page43.
Schedule
Indicates if the desired leaving water temperature is according to a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:
In Fixed LWT setpoint mode, the scheduled actions consist of
desired leaving water temperatures, either preset or custom.
In Weather dependent LWT setpoint mode, the scheduled actions
consist of desired shift actions, either preset or custom.
# Code Description
[2.1] N/A Schedule
0: No
1: Yes
Heating schedule
You can set the main zone heating temperature schedule using the
schedule screen. For more information about this screen, see
"8.3.8Schedule screen: Example"on page44.
Cooling schedule
You can set the main zone cooling temperature using the schedule
screen. For more information about this screen, see "8.3.8Schedule
screen: Example"on page44.
Setpoint mode
In Fixed mode, the desired leaving water temperature does NOT
depend on the outdoor ambient temperature.
In WD heating, fixed cooling mode, the desired leaving water
temperature:
depends on the outdoor ambient temperature for heating
does NOT depend on the outdoor ambient temperature for cooling
In Weather dependent mode, the desired leaving water temperature
depends on the outdoor ambient temperature.
# Code Description
[2.4] N/A Setpoint mode
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
When weather dependent operation is active, low outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift the
water temperature up or down by a maximum of 10°C.
Heating WD curve
Set weather-dependent heating for the main zone (if [2.4] = 1 or 2):
# Code Description
[2.5] [1-00]
[1-01]
[1-02]
[1-03]
Set weather-dependent heating:
[1-03]
[1-02]
T
a
T
t
[1-00] [1-01]
T
t
: Target leaving water temperature
(main zone)
T
a
: Outdoor temperature
[1-00]: Low outdoor ambient
temperature. –40°C~+5°C
[1-01]: High outdoor ambient
temperature. 10°C~25°C
[1-02]: Desired leaving water
temperature when the outdoor
temperature equals or drops below the
low ambient temperature.
[9‑01]°C~[9‑00]°C
Note: This value should be higher
than [1‑03] as for low outdoor
temperatures warmer water is
required.
[1-03]: Desired leaving water
temperature when the outdoor
temperature equals or rises above the
high ambient temperature.
[9‑01]°C~min(45, [9‑00])°C
Note: This value should be lower than
[1‑02] as for high outdoor
temperatures less warm water is
required.
Cooling WD curve
Set weather-dependent cooling for the main zone (if [2.4] = 2):

Table of Contents

Other manuals for Daikin Altherma EAVX-D9WG

Related product manuals