8 Configuration
Installer reference guide
51
EPGA11~16DAV3 + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556070-1 – 2019.02
8.4.4 Additional zone
Setpoint screen
You can set the leaving water temperature for the additional zone
using the setpoint screen. For more information about how to do this,
see "8.3.5Setpoint screen"on page43.
Schedule
Indicates if the desired leaving water temperature is according to a
schedule. Also see "8.4.3Main zone"on page47.
# Code Description
[3.1] N/A Schedule
0: No
1: Yes
Heating schedule
You can set the additional zone heating temperature schedule using
the schedule screen. For more information about this screen, see
"8.3.8Schedule screen: Example"on page44.
Cooling schedule
You can set the additional zone cooling temperature using the
schedule screen. For more information about this screen, see
"8.3.8Schedule screen: Example"on page44.
Setpoint mode
The setpoint mode of the additional zone can be independently set
from the setpoint mode of the main zone, see " Main zone" on
page47.
# Code Description
[3.4] N/A Setpoint mode
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
Heating WD curve
Set weather-dependent heating for the additional zone (if [3.4] = 1 or
2):
# Code Description
[3.5] [0-00]
[0-01]
[0-02]
[0-03]
Set weather-dependent heating:
[0-00]
[0-01]
T
a
T
t
[0-03] [0-02]
T
t
: Target leaving water temperature
(additional zone)
T
a
: Outdoor temperature
[0-03]: Low outdoor ambient
temperature. –40°C~+5°C
[0-02]: High outdoor ambient
temperature. 10°C~25°C
[0-01]: Desired leaving water
temperature when the outdoor
temperature equals or drops below the
low ambient temperature.
[9‑05]°C~[9‑06]°C
Note: This value should be higher
than [0‑00] as for low outdoor
temperatures warmer water is
required.
[0-00]: Desired leaving water
temperature when the outdoor
temperature equals or rises above the
high ambient temperature.
[9‑05]~min(45, [9‑06])°C
Note: This value should be lower than
[0‑01] as for high outdoor
temperatures less warm water is
required.
Cooling WD curve
Set weather-dependent cooling for the main zone (if [3.4] = 2):