13 Disposal
Installer reference guide
83
EPGA11~16DAV3 + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556070-1 – 2019.02
13.5.3 To handle the stem cap
The stem cap is sealed where indicated with the arrow. Do NOT
damage it.
After handling the stop valve, tighten the stem cap, and check for
refrigerant leaks.
Item Tightening torque (N∙m)
Stem cap, liquid side 13.5~16.5
Stem cap, gas side 22.5~27.5
13.5.4 To handle the service cap
ALWAYS use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
After handling the service port, tighten the service port cap, and
check for refrigerant leaks.
Item Tightening torque (N∙m)
Service port cap 11.5~13.9