7 | Unit installation
Installer reference guide
75
EVLQ05+08CA + EHYHBH05A + EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
7.6.6 Flue pipe position
See the local and national regulations.
Especially for UK:
Only use flue products approved by the boiler manufacturer, which can be bought
from the supplier of your boiler.
See "6.2Combining units and options"[437].
Terminal position Minimum distance
(mm)
A Directly below an open able window or other
opening (e.g. air brick)
300
B Below gutters, soil pipes or drain pipes 75
C Below eaves 200
D Below balconies or car front roofs
E From vertical drain pipes and soil pipe 150
F From internal or external corners 300
G Above ground, roof or balcony level
H From a surface facing a terminal 600