8 Configuration
Installation and operation manual
27
EHYKOMB33A
Daikin Altherma hybrid heat pump – gas boiler module
4P353067-1H – 2018.10
Parameter Setting Range Default
settings
Description
Installation type 0~3 0 0=Combi
1=Heating only + external domestic
hot water tank
2=Domestic hot water only (no
heating system required)
3=Heating only
It is recommended not to modify this
setting.
Space heating pump continuous 0~3 0 0=Post purge period only
1=Pump continuously active
2=Pump continuously active with
MIT switch
3=Pump on with external switch
This setting has no effect.
Maximum space heating power set ~85% 70% Maximum power in heating. This is a
percentage of the maximum set in
parameter . We strongly recommend
not modifying this setting.
. Maximum capacity space heating
pump
80 There is no space heating pump in the
gas boiler. Changing this setting has
no effect.
Maximum domestic hot water power
set
(not applicable for Switzerland)
~100% 100% Maximum power in instant domestic
hot water. This is a percentage of the
maximum set in parameter . Because
of the 2-digit display, the highest
displayable value is 99. It is however
possible to set this parameter to 100%
(default setting). We strongly
recommend not modifying this setting.
Minimum supply temperature of the
heat curve
10°C~25°C 15°C Do NOT modify this setting on the
boiler. Use the user interface instead.
. Maximum supply temperature of the
heat curve
30°C~90°C 90°C Do NOT modify this setting on the
boiler. Use the user interface instead.
Minimum outside temperature of the
heat curve
–30°C~10°C –7°C Do NOT modify this setting on the
boiler. Use the user interface instead.
Maximum outside temperature of the
heat curve
15°C~30°C 25°C Do NOT modify this setting on the
boiler. Use the user interface instead.
Space heating pump post purge period 0~15min 1min Changing this setting has no effect on
the operation of the unit.
Space heating pump post purge period
after domestic hot water operation
0~15min 1min Changing this setting has no effect on
the operation of the unit.
Position 3-way valve or electric valve 0~3 0 0=Powered during space heating
1=Powered during domestic hot
water
2=Powered during every heat
demand (space heating, domestic
hot water, eco/comfort)
3=Zone regulation
4 and higher=Not applicable
Booster 0~1 0 Changing this setting has no effect on
the operation of the unit.
Step modulation 0~1 1 0=OFF during space heating
operation
1=ON during space heating
operation
It is recommended not to modify this
setting.