Troubleshooting by Indication on the Remote Controller ESIE09-08A
214 Troubleshooting
3.59 “U7 Indoor Unit: Malfunction of Transmission Outdoor Unit
Remote Control
Display
U7
Subcode 2
Applicable Models ER*Q 011~016*
Method of
Malfunction
Detection
Microcomputer checks the transmission of outdoor unit.
Malfunction
Decision Conditions
When transmission is not carried out normally for a certain amount of time
Supposed Causes Improper connection of transmission wiring between outdoor unit and external control adaptor for
outdoor unit
Improper cool/heat selection
Improper cool/heat unified address (outdoor unit, external control adaptor for outdoor unit)
Defect of outdoor unit PC board (A1P)
Defect of external control adaptor for outdoor unit
Troubleshooting
Caution
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
(V2824)
C/H
SELECT is set to “IND”.
Replace the outdoor unit PC
Board (A1P).
YES
Cool/heat selection is
unified.
Set C/H SELECT to “IND”.
NO
NO
C/H SELECT is set to
“MASTER”.
C/H SELECT is set to
“SLAVE”.
Set C/H SELECT to “IND”.
YES
YES
Set C/H SELECT to “IND”.
Replace the outdoor unit PC
board (A1P).
NO
NO
YES
( )
( )
( )
( ) To select “IND”, press the BS2 button (set) till H3P led is on. Then press BS3 button (return) to confirm.