IO-DAPPS www.daikinac.com 12
Procedure Steps Display
Change the override setpoint
Entering an override setpoint can only take place if the BACnet™
Thermostat is in the unoccupied mode.
1. Push the buon under unoccupied icon .
NOTE: If a user password has previously been set up with a user
password, entering a password is not required.
2. Press either the ▲ or ▼ buon to change the rst digit of the
password.
3. Press the Enter buon to select the next digit of the password.
4. Press either the ▲ or ▼ buon to turn the override ON or OFF.
• Override O – The controller uses the unoccupied setpoint as
the acve setpoint
• Override On – The controller changes to the occupied setpoint
which can then be temporarily changed
5. Press the Enter buon to save the seng.
NOTE: When the system is in the unoccupied mode, changing the
acve setpoint will automacally place the system in the override
mode.
Change the display units
To temporarily change the display units to either Celsius or
Fahrenheit, press and hold the middle buon under the display unl
the units change.
Program Set-Up