EasyManua.ls Logo

Daikin BACnet Series - Setting Up Communications

Daikin BACnet Series
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IO-DAPPS www.daikinac.com 15
Set Up Communicaons
Seng BACnet™ communicaons properes is required only if the
BACnet Thermostat is integrated into a network with other BACnet
controllers. Entering the communicaons properes requires
entering Password 2.
Table 8: Set Up Communicaons
Procedure Steps Display
Starng display
1. Start at the temperature display.
2. Enter Password 2. The display changes to the MAIN menu display.
Change the network communicaon properes
1. From the MAIN menu, press either the or buon to
select COMM.
2. Press Enter. The COMM menu opens up.
3. Choose and set the following properes.
DEVICE ID – This is the BACnet device instance. The device
instance must be within the range of 1 to 4,194,302.
MAC – The MAC address must be in the range of 1 – 127.
BAUD – Set to match other devices on the BACnet MS/TP
network. The choices are Auto, 9600, 19200, 38400, or 76800.
NOTE: Aer changing a communicaon property the BACnet
Thermostat will reset.
NOTE: If seng up with the MicroTech Integrated System contact a
Daikin representave for the appropriate values.
Program Set-Up

Related product manuals