EasyManua.ls Logo

Daikin BACnet Series - System Integration; Connecting to a Network

Daikin BACnet Series
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IO-DAPPS www.daikinac.com 29
Topics in this secon cover integrang BACnet™ Thermostat controllers
into a building automaon network. These are advanced topics for
control technicians and engineers. The BACnet Thermostat can funcon
as a stand-alone controller or it can be connected to a BACnet MS/TP
network. The topics in this secon are reference material for control
technicians or engineers that will be installing and seng up a BACnet
Thermostat that is connected to a network.
Connecng to a Network
Before connecng the BACnet Thermostat to a BACnet MS/TP
network, congure the network properes. See the topic Set Up
Communicaons on page 15 for the procedure to set the following.
Device Instance
MAC address
Baud
Use the following principles when wiring the BACnet Thermostat to an
MS/TP network:
Connect no more than 128 addressable BACnet devices to one
MS/TP network.
Use 18 gauge, twisted pair, shielded cable for all network wiring.
Connect the (–A) terminal in parallel with all other (–) terminals.
Connect the (+B) terminal in parallel with all other (+) terminals.
Connect the shield to an earth ground at only one locaon on
the network.
The controllers or devices on the physical ends of the MS/TP wiring
segment must have end-of-line (EOL) terminaon installed for proper
network operaon. Set the end-of-line terminaon to ‘On’ using
the EOL switches. A 120Ω resistor across the posive and negave
communicaon wires will also work as an EOL terminaon.
Figure 12: BACnet MS/TP Network Wiring
Figure 13: Locaon of EOL switch
Applicaon Drawings

Related product manuals