ENGLISH
5
! NOTE
The LED will blink if error occurred.–
If there is any abnormal condition detected, BRC51D controller will blink the error code. The format
for the error code will be as following:
DX Error Code
ERROR
CODE
MEANING
E01 Room Sensor Open or Short
E02 Indoor Coil Sensor Open
E03 Outdoor Coil Sensor Open
E04 Compressor Overload/Indoor Coil Sensor Short/Outdoor Coil Sensor Short
E05 Low Refrigerant Charge/Gas Leak/Outdoor Abnormal
E06 Water Pump Fault
E07 Outdoor Coil Sensor Exist (MS model)
E08 Hardware Error (Tact Switch Pin Short)
E09 Indoor Fan Feedback Error
EE EEPROM Error
CW Error Code
ERROR
CODE
MEANING
E01 Room Sensor Open or Short
E02 Pipe Water Sensor Open or Short
E04 Pipe Water Temperature Poor
E05 Pipe Water Temperature Bad/Fault
E06 Water Pump Error
E08 Hardware Error (Tact Switch Pin Short)
E09 Indoor Fan Feedback Error
For Inverter Only
ERROR
CODE
MEANING
00 Normal
A1 Indoor PCB Error
A3 Drain Pump Abnormal
A5 Antifreeze (Cooling)/Heat Exchanger Overheat (Heating)
A6 Indoor Fan Motor Abnormal
AH Electrical Air Cleaner Abnormal
C4 Indoor Heat Exchanger (1) Thermistor Short/Open
C5 Indoor Heat Exchanger (2) Thermistor Short/Open
C7 Louver Limit Switch Error
C9 Indoor Room Thermistor Short/Open
ERROR INDICATOR
1-OM-BRC51D-0616(2)-DAIKIN-EN.in5 51-OM-BRC51D-0616(2)-DAIKIN-EN.in5 5 8/12/20 3:41:43 PM8/12/20 3:41:43 PM