Application Information
3) Cable Size
Cooling only
Model Unit
FFN10CV1 FFN15CV1 FCN20FV1
RN10FV1 RN15FV1 RN20CV1
Power supply cable size
Number of wire
mm²
1.5
3
1.5
3
2.5
3
Interconnection cable size
Number of wire
mm²
1.5
3
1.5
3
2.5
3
Recommended fuse A 15 15 16
Model Unit
FCN25FV1 FCN30FV1
RN25CV1 RN28CV1 RN30CV1
Power supply cable size
Number of wire
mm
2
2.5
3
2.5
3
2.5
3
Interconnection cable size
Number of wire
mm
2
2.5
3
2.5
3
2.5
3
Recommended fuse A 20 25 25
Model Unit
FCN35FV1
RN35DV1
Power supply cable size
Number of wire
mm
2
4.0
3
Interconnection cable size
Number of wire
mm
2
2.5
4
Recommended fuse A 25
Model Unit
FCN40FV1 FCN50FV1
RN40DY1 RN50DY1
Power supply cable size mm
2
4.0 4.0
Number of wire 3 3
Interconnection
cable size
Indoor mm
2
2.5 2.5
Outdoor mm
2
2.5 2.5
Number of wire
Indoor 4 4
Outdoor 4 + 3 4 + 3
Recommended fuse A 16 20