5
English
(1) Install the indoor unit temporarily.
• Fix the hanger bracket to the suspension bolt.
Make sure to securely x the hanger bracket with the
nut and the washer for hanger bracket (3) from the up-
per and lower side. (Refer to Fig. 7)
If the washer xing plate (7) is used, the upper side
washer for hanger bracket (3) may be protected from
falling off.
(Refer to Fig. 8)
[To fix hanger bracket] Suspension bolt
Washer for hanger bracket (3)
(Accessory)
Hanger bracket
Tighten the nut
Nut
(Field supply)
Fig. 7
[To fix washer fixing plate]
Washer fixing plate (7)
(Accessory)
Upper side nut
(Field supply)
Insert
Fig. 8
(2)
• The installation pattern paper (5) is matched to the ceil-
ing opening dimension.
For the height of ceiling lower surface from the oor
level, conrm with the builder of ceiling.
• The center of the ceiling opening is shown in the instal-
lation pattern paper (5).
The center of the indoor unit is indicated as triangle
marks on the sides and bottom of the unit and those on
the installation pattern paper (5).
• Put the installation pattern paper (5) to the indoor unit
with four screws (6).
At this time, put the installation pattern paper (5) to the
indoor unit with the triangle marks on the indoor unit
and those on the installation pattern paper (5) aligned.
Installation
pattern
paper (5)
(Accessory)
[Installation of the installation pattern paper]
Center of
ceiling opening
Screw (6)
(Accessory)
Screw (6)
(Accessory)
indoor unit
Center mark
of the unit
< Installation work after the ceiling work is nished >
(3) Adjust the indoor unit to be located at the correct posi-
tion.
(Refer to 3. PREPARATION BEFORE INSTALLATION
– (1))
• Using the Installation guide (15) allows you to check
the position from the underside of the unit to the lower
ceiling surface.
Apply the short
side of the
cut-out section.
Installation guide (15)
(Accessory)
Underside
of the unit
[For BYCQ54EEFU]
[For BYCQ54EEGFU]
Cut away the 1st and 2nd
notches and apply.
Underside
of the unit
Installation guide (15)
(Accessory)
(4) Check the level of the unit. (Refer to Fig. 9)
(5) Remove the washer xing plate (7) used for preventing
the washer for hanger bracket (3) from dropping and
tighten the upper side nut.
(6) Remove the installation pattern paper (5).
Level
Vinyl tube
[Maintaining horizontality]
Fig. 9
01_EN_3P693452-2.indd 5 2022/08/09 16:00:11