EasyManua.ls Logo

Daikin FH100BVE - Page 379

Daikin FH100BVE
501 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Si20-701_B Troubleshooting by Remote Controller
372
NO
YES
Monitor the
voltage
(Instantaneous
voltage drop)
Replace the
outdoor unit
PCB.
Is the
measured voltage
220 VDC or
more?
A
When the compressor is
running, measure the
voltage between + and -
of electrolytic capacitor
(C+, C-).

Table of Contents

Related product manuals