2 | Components
Service manual
135
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
d
d
c
e
a
b
c dc d ee
e
cA
A RXA42~50A unit
a L803
b L804
c Measuring point
d Measuring point
e Measuring point
d
dc
e
a
b
c
d
c
d
e
e
e
c
A
A RXA42~50B unit
a L803
b L804
c Measuring point
d Measuring point
e Measuring point
Is the resistance measurement correct? Action
Yes Proceed with the next step.
No Replace the reactor, see "2.15.2Repair
procedures"[4136].
4 Measure the inductance of the reactor using an LCR meter.
Result: The inductance MUST be as follows:
Measuring points Resistance
c‑d 88.5~101.5µH