EasyManua.ls Logo

Daikin FTXA20AW - 3 Third Party Components; Electrical Circuit; Checking Procedures

Daikin FTXA20AW
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 | Third party components
Service manual
156
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
3 Third party components
3.1 Electrical circuit
3.1.1 Checking procedures
To check the power supply of the unit
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see "2.14Plate work"[4120].
1 Check that the power supply cables and earth connection are firmly fixed to
the power supply terminal X1M.
2 Measure the insulation resistance between each power supply terminal and
the ground using a megger device of 500 V DC. All measurements MUST be
>1MΩ. If insulation resistance is <1MΩ, earth leakage is present.
3 Turn ON the power using the respective circuit breaker.
4 Measure the voltage between L and N on the power supply terminal X1M.
Result: The voltage MUST be 230VAC ± 10%.
5 Unbalance between the phases MUST NOT exceed 2%.
Is the measured voltage (power supply)
correct?
Action
Yes Return to the troubleshooting of the
specific error and continue with the
next procedure.
No Adjust the power supply, see
"3.1.2Repair procedures"[4157].
To check the power supply to the indoor unit
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Remove the required plate work, see "2.14Plate work"[4120].
2 Check that the power supply cables and earth connection are firmly fixed to
the indoor unit power supply terminal X1M.
3 Turn ON the power using the respective circuit breaker.
4 Measure the voltage between L and N on the indoor unit power supply
terminal X1M.
Result: The voltage MUST be 230VAC ± 10%.
Is the measured voltage (power supply)
correct?
Action
Yes Return to the troubleshooting of the
specific error and continue with the
next procedure.
No Continue with the next step.
5 Check the power supply to the unit, see "3.1.1Checking procedures"[4156].

Table of Contents

Related product manuals