EasyManua.ls Logo

Daikin FTXA20AW - Page 55

Daikin FTXA20AW
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 | Components
Service manual
55
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
a
a
b
c
c
c
a
a Nut
b Compressor
c Damper
INFORMATION
The compressor dampers may look different.
7 Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02MPa.
8 Wrap a wet rag around the compressor pipes and any other components near
the compressor and solder the compressor pipes to the refrigerant pipes.
a
a
a Compressor pipe
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
9 After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
10 Connect the Faston connectors to the compressor wire terminals U, V and W

Table of Contents

Related product manuals