EasyManua.ls Logo

Daikin FTXA20C2V1BW - Specifications of Standard Wiring Components

Daikin FTXA20C2V1BW
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 | Electrical installation
Installer reference guide
41
CTXA-C(W)(B)(S) + FTXA-C(W)(B)(S)
Daikin room air conditioner
4P518023-15P – 2023.05
Method 2: Using round crimp-style terminal
1 Strip insulation from wires and slightly twist the end of each wire.
2 Install a round crimp-style terminal on the end of the wire. Place the round
crimp-style terminal on the wire up to the covered part and fasten the
terminal with the appropriate tool.
Use the following methods for installing wires:
Wire type Installation method
Single-core wire
Or
Stranded conductor wire
twisted to "solid-like"
connection
c b
c
aa
A
AA´
a Curled wire (single-core or twisted stranded
conductor wire)
b Screw
c Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3
8.1.3 Specifications of standard wiring components
Component
Interconnection cable
(indoor↔outdoor)
Voltage 220~240V
Wire size Only use harmonized wire
providing double insulation and
suitable for applicable voltage
4-core cable
Minimum 1.5mm²