1 | Troubleshooting
Service manual
11
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
1 Perform a check of the indoor unit heat exchanger thermistor. See
"2.19Thermistors"[4144].
Possible cause: Faulty indoor unit heat exchanger thermistor.
2 Perform a check of the indoor unit main PCB. See "2.8 Indoor unit main
PCB"[475].
Possible cause: Faulty indoor unit main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.6 C9-00 – Room thermistor abnormality
Trigger Effect Reset
Resistance value is out of
range. Temperature
measured <–43.6°C or
>90°C.
Unit will stop operating. Automatic reset when
resistance is within range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the indoor unit air (room) thermistor. See
"2.19Thermistors"[4144].
Possible cause: Faulty indoor unit air (room) thermistor.
2 Perform a check of the indoor unit main PCB. See "2.8 Indoor unit main
PCB"[475].
Possible cause: Faulty indoor unit main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.7 CC-00 – Humidity sensor abnormality
Trigger Effect Reset
Disconnected sensor
Broken sensor
Communication error
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the humidity sensor. See "2.6Humidity sensor"[470].
Possible cause: Faulty humidity sensor.