EasyManua.ls Logo

Daikin FTXA25AW - Field Settings; To Control Heating Only Mode; To Adjust Target Set Temperature in Heating Operation

Daikin FTXA25AW
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 | Technical data
Service manual
189
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
5.7 Field settings
5.7.1 To control heating only mode
Prerequisite: Stop operation of the unit.
1 Press
, , and simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 19.
7 Press
to confirm.
8 Press
.
9 Select 1 (0: factory setting, 1: heating only).
10 Press
to confirm.
5.7.2 To adjust target set temperature in heating operation
INFORMATION
When there is a big difference between the indoor room temperature and the set
temperature in heating mode, adjust the target set temperature field setting.
Target temperature = remote controller set temperature + 2.5°C. For
example:
Remote controller set temperature = 20°C
Target temperature = 20°C + 2.5°C = 22.5°C
Thermo off temperature = 24.5°C
1 Press
, , and simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 7.
7 Press
to confirm.
8 Press
.
9 Select the value to set the desired target temperature:
0 = –2,0°C
1 = –1,0°C
2 = 0°C (factory setting)
3 = +1,0°C
4 = +2,0°C
10 Press
to confirm.

Table of Contents

Related product manuals