Service Diagnosis
33
Last State Error retrieved by remote controller BRC52A61 & BRC52B63
Operating Guide
1. Remove battery from remote controller.
2. Replace battery again into remote controller.
3. Press Mode & ON/OFF buttons together.
4. The“ ” will show at temperature section.
5. Press Mode button to 5:00.
6. Press Power On toward the indoor unit. Unit LED blinks two times indicate received signal.
7. ON hold fan button till screen become normal display.
8. Repeat the normal step to retrieve error. (by using remote controller step. Holding TIMER CANCEL…)
9. By using this method, the error shown will be Last State Error. (Previous error in the unit)
3.2.2 Wired controller BRC51A61
The error will show at the LCD display.
Last State Error retrieved by wired controller BRC51A61
PressSLEEP&TIMERACTIVEsimultaneouslyfor5secondsandtheerrorwillash.
Remark : Wired controller is an optional accessory