5 | Third party components
Service manual
63
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04 – 2022.04
a
b
a Liquid stop valve
b Gas stop valve
2 Check if the stop valves are completely open.
The refrigerant circuit stop valves are
open?
Action
Yes Return to the troubleshooting of the
specific error and continue with the
next procedure.
No Open the stop valves of the refrigerant
circuit, see "5.2.2Repair
procedures"[467].
To check if the refrigerant circuit is clogged
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Wait for the refrigerant to reach the outdoor temperature.
2 Check that all field piping is done according to the refrigeration practice and
installer reference guide:
Correct piping diameters
Piping distance limits are followed
NO pipes are squeezed
NO short radius bends
3 Connect a manometer to the service port.
4 Turn ON the power of the unit.
5 Activate Heating operation via the user interface.
6 Read the pressure on the pressure gauge. If, at the start of the unit operation,
the pressure is high or very low, the refrigerant circuit might be clogged.
7 On the refrigerant liquid piping (between the indoor unit heat exchanger and
the outdoor unit heat exchanger (coil)), using a contact thermometer,
measure the temperature before and after every restricting device. If a big
temperature difference is measured (>2.5~4K), an internal pipe obstruction
may be present at this location.
draft–22/04/2022 08:50