EasyManua.ls Logo

Daikin FTXN09KEVJU - Heat Pump Capacity Tables

Daikin FTXN09KEVJU
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDUS041111_a Capacity Tables
Room Air Conditioners K-Series 23
FTXN24KVJU + RKN24KEVJU (60 Hz, 230 V)
3D071298
AFR 16.2
BF 0.23
Temp: Celsius
TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.06.104.301.966.104.302.155.954.222.345.834.152.425.654.062.534.953.702.38
16.022.06.854.461.976.554.312.166.254.162.356.134.102.435.944.012.545.223.662.38
18.025.07.144.621.986.844.472.176.544.332.366.424.282.446.244.192.555.493.862.38
19.426.77.354.611.997.054.482.186.754.342.376.634.292.45
6.45 4.21 2.56 5.69 3.88 2.38
22.030.07.744.632.017.444.502.207.144.382.397.024.342.466.844.262.576.043.962.38
24.032.08.034.492.027.734.382.217.434.272.407.314.222.477.134.162.596.313.872.38
Temp: Fahrenheit
TC, SHC: kBtu/h
PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 89.6 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 20.83 14.67 1.96 20.83 14.67 2.15 20.29 14.38 2.34 19.88 14.17 2.42 19.27 13.85 2.53 16.88 12.62 2.38
60.8 71.6 23.36 15.22 1.97 22.33 14.70 2.16 21.31 14.18 2.35 20.90 13.98 2.43 20.28 13.67 2.54 17.81 12.48 2.38
64.4 77.0 24.37 15.75 1.98 23.35 15.26 2.17 22.32 14.78 2.36 21.91 14.59 2.44 21.30 14.31 2.55 18.74 13.16 2.38
67.0 80.0 25.08 15.74 1.99 24.06 15.28 2.18 23.03 14.82 2.37 22.62 14.64 2.45
22.00 14.37 2.56 19.40 13.25 2.38
71.6 86.0 26.40 15.79 2.01 25.37 15.37 2.20 24.35 14.96 2.39 23.94 14.79 2.46 23.33 14.55 2.57 20.61 13.51 2.38
75.2 89.6 27.41 15.32 2.02 26.39 14.93 2.21 25.36 14.56 2.40 24.95 14.41 2.47 24.34 14.18 2.59 21.54 13.20 2.38
Symbols: Note:
AFR : Airflow rate (m
3
/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the
tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with
around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25 ft
Level difference : 0 ft
6. Cooling capacity at
15°CDB and 5°FDB.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heat capacity (kW) / (kBtu/h)
PI : Power input (kW)
Temp: Celsius
TC, SHC, PI: kW
INDOOR OUTDOOR
EWB EDB –15 (°CDB)
°C °C TC SHC PI
14.0 20.0 4.84 3.70 0.59
Temp: Fahrenheit
TC, SHC: kBtu/h
PI: kW
INDOOR OUTDOOR
EWB EDB 5 (°FDB)
°F °F TC SHC PI
57.2 68.0 16.52 12.63 0.59

Table of Contents

Other manuals for Daikin FTXN09KEVJU

Related product manuals