SiUS041111 Control Specification
Function and Control 41
3.6 Freeze-up Protection Control
Outline During cooling operation, the signal sent from the indoor unit controls the operating frequency
limitation and prevents freezing of the indoor heat exchanger. (The signal from the indoor unit is
divided into zones.)
Detail The operating frequency limitation is judged with the indoor heat exchanger temperature.
3.7 Heating Peak-cut Control
Outline During heating operation, the indoor heat exchanger temperature determines the frequency upper
limit to prevent abnormal high pressure.
Detail
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is canceled.
09/12 class 15/18/24 class
A 65°C (149°F) 60°C (140°F)
B 51°C (123.8°F) 54°C (129.2°F)
C 48°C (118.4°F) 51°C (123.8°F)
D 46°C (114.8°F) 49°C (120.2°F)
E 41°C (105.8°F) 44°C (111.2°F)