EasyManua.ls Logo

Daikin FTXN15KVJU - Signal Transmission Error (between Indoor Unit and Outdoor Unit)

Daikin FTXN15KVJU
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting SiUS041111
86 Service Diagnosis
4.6 Signal Transmission Error (between Indoor Unit and
Outdoor Unit)
Remote
Controller
Display
U4
Method of
Malfunction
Detection
The data received from the outdoor unit in indoor unit - outdoor unit signal transmission is checked
whether it is normal.
Malfunction
Decision
Conditions
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Supposed
Causes
Wiring error
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Defective outdoor unit PCB
Defective indoor unit PCB
Disturbed power supply waveform

Table of Contents

Other manuals for Daikin FTXN15KVJU

Related product manuals