Capacity Tables EDUS041111_a
22 Room Air Conditioners K-Series
FTXN18KVJU + RKN18KEVJU (60 Hz, 230 V)
3D071297
AFR 16.2
BF 0.23
Temp: Celsius
TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.05.363.911.155.113.781.264.873.661.374.773.611.424.623.541.484.383.421.50
16.022.05.603.841.165.363.721.275.113.611.385.013.561.424.873.491.494.623.381.50
18.025.05.854.011.165.603.901.275.363.801.385.263.751.435.113.691.504.863.581.51
19.426.76.024.021.175.773.921.285.533.821.395.433.781.43
5.28 3.72 1.50 5.03 3.62 1.51
22.030.06.334.071.186.093.981.295.843.881.405.743.851.445.603.791.515.353.701.52
24.032.06.583.961.186.333.871.296.093.791.405.993.761.455.843.711.525.593.631.53
Temp: Fahrenheit
TC, SHC: kBtu/h
PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 89.6 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 18.29 13.34 1.15 17.45 12.91 1.26 16.61 12.49 1.37 16.28 12.32 1.42 15.77 12.07 1.48 14.94 11.66 1.50
60.8 71.6 19.12 13.11 1.16 18.28 12.71 1.27 17.44 12.31 1.38 17.11 12.15 1.42 16.60 11.92 1.49 15.77 11.53 1.50
64.4 77.0 19.95 13.70 1.16 19.11 13.32 1.27 18.27 12.95 1.38 17.94 12.81 1.43 17.43 12.59 1.50 16.60 12.23 1.51
67.0 80.0 20.53 13.73 1.17 19.69 13.38 1.28 18.85 13.03 1.39 18.52 12.89 1.43
18.00 12.68 1.50 17.18 12.34 1.51
71.6 86.0 21.61 13.89 1.18 20.77 13.57 1.29 19.93 13.25 1.40 19.60 13.13 1.44 19.09 12.94 1.51 18.26 12.64 1.52
75.2 89.6 22.44 13.51 1.18 21.60 13.22 1.29 20.76 12.93 1.40 20.43 12.82 1.45 19.92 12.65 1.52 19.09 12.37 1.53
Symbols: Note:
AFR : Airflow rate (m
3
/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the
tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with
around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25 ft
Level difference : 0 ft
6. Cooling capacity at
15°CDB and 5°FDB.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heat capacity (kW) / (kBtu/h)
PI : Power input (kW)
Temp: Celsius
TC, SHC, PI: kW
INDOOR OUTDOOR
EWB EDB –15 (°CDB)
°C °C TC SHC PI
14.0 20.0 4.84 3.70 0.59
Temp: Fahrenheit
TC, SHC: kBtu/h
PI: kW
INDOOR OUTDOOR
EWB EDB 5 (°FDB)
°F °F TC SHC PI
57.2 68.0 16.52 12.63 0.59