Electric Characteristics EDUS041111_a
42 Room Air Conditioners K-Series
10.Electric Characteristics
3D072397
3D071278
Indoor Unit Outdoor Unit
Power Supply COMP OFM IFM
Hz - Volts Voltage Range MCA MOP RHz RLA W FLA W FLA
FTXN09KEVJU RKN09KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
4.3 15
—
3.6
33
0.19
16
0.20
60 - 230 3.3 0.17 0.18
FTXN12KEVJU RKN12KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
7.0 15
—
6.1
33
0.19
16
0.20
60 - 230 5.5 0.17 0.18
FTXN15KVJU RKN15KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
15.0 20 56
5.6
60 0.30 43 0.25
60 - 230 5.0
FTXN18KVJU RKN18KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
15.0 20 68
6.8
60 0.30 43 0.25
60 - 230 6.1
FTXN24KVJU RKN24KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
15.0 20 98
12.0
60 0.30 43 0.25
60 - 230 10.8
FTXN09KEVJU RXN09KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
4.8 15
—
4.1
33
0.19
16
0.20
60 - 230 3.7 0.17 0.18
FTXN12KEVJU RXN12KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
7.0 15
—
6.1
33
0.19
16
0.20
60 - 230 5.5 0.17 0.18
FTXN15KVJU RXN15KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
15.5 20 56
5.6
60 0.30 43 0.25
60 - 230 5.0
FTXN18KVJU RXN18KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
15.5 20 68
6.8
60 0.30 43 0.25
60 - 230 6.1
FTXN24KVJU RXN24KEVJU
60 - 208
MAX. 60 Hz 253 V
MIN. 60 Hz 187 V
15.5 20 98
12.0
60 0.30 43 0.25
60 - 230 10.8
Symbols: Note:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. : 27°CDB / 19°CWB (80.6°FDB / 66.2°FWB)
Outdoor temp. : 35°CDB (95°FDB)
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4.
MOP : Max. overcurrent protection (A)
RHz : Rated operating frequency (Hz)
RLA : Rated load amps (A)
OFM : Outdoor fan motor
IFM : Indoor fan motor
W : Fan motor rated output (W)
FLA : Full load amps (A)