EasyManua.ls Logo

Daikin FTXN50L - Page 61

Daikin FTXN50L
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service Diagnosis
53
H6 (RXN25/35M/N, RXK25/35A)
Description
POSITION SENSOR ABNORMAL (COMPRESSOR)
Possible Root
cause
1. Compressor relay cable disconnected.
2. Compressor itself defective.
3. Outdoor PCB defective.
4. Stop valve closed.
5. Inputvoltageoutofspecication.
Troubleshooting
Normal?
Electricals or
compressor harnesses
connected as
specified?
No
Yes
Check for short circuit.
Check with inverter checker (*).
Check the electrolytic capacitor
voltage.
Turn off the power. Disconnect
the harness U, V and W.
Replace the outdoor unit
PCB, outdoor unit fan.
DC320 ± 30 V?
No
Yes
No
Any LED off?
Yes
Correct the power supply or
replace the outdoor unit PCB.
No
Reconnect as specified.
* Inverter checker
Part No.: 1225477
Replace the outdoor unit PCB.
Replace the compressor.

Related product manuals