EasyManuals Logo

Daikin FUY125FJV1 User Manual

Daikin FUY125FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #306 background imageLoading...
Page #306 background image
Troubleshooting by Remote Controller Si20-701_B
299
A
Check the power
transistor on the inverter
PCB using a multiple
tester.
Connect the compressor
cable, and then restart the
operation.
Does
the power
transistor have any
abnormalities?
Is a
difference
between high
pressure and low
pressure prior to
startup
0.2MPa?
The error
is displayed again.
Replace the
inverter PCB.
∗The inverter is
likely to have
got defective
due to the error
of the
compressor.
After the
completion of
replacement,
be sure to
check the
compressor.
End of
measures:
Check the
refrigerant
system.
Check of
compressor:
Check the
compressor for
abnormal
sounds,
vibration,
operating
conditions, and
others according
to the
Compressor
Diagnosis
Procedure.
Defective
pressure
equalization:
Check the
refrigerant
system.
Power
OFF
Power
ON
YES
YES
NO
YES
NO
NO
It can take a
maximum of
60 minutes to
determine the
error.

Table of Contents

Other manuals for Daikin FUY125FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY125FJV1 and is the answer not in the manual?

Daikin FUY125FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY125FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals