111
Engineering & Physical Data
Engineering Data - Chilled Water Fan Coil Unit
MODEL
FWKE11E
HIGH MEDIUM LOW QUIET
NOMINAL COOLING CAPACITY
Btu/h 40100 33100 26800 21000
W 11750 9700 7850 6150
NOMINAL SENSIBLE COOLING CAPACITY
Btu/h 28600 23800 18900 14600
W 8370 6970 5540 4270
NOMINAL HEATING CAPACITY
(ENTERING WATER TEMP. = 50°C)
Btu/h 46700 39100 31600 24100
W 13700 11450 9250 7050
FAN INPUT POWER W 120 83 39 23
NOMINAL RUNNING CURRENT A 0.95 0.55 0.35 0.21
POWER SOURCE V/Ph/Hz 220-240/1/ 50
INDOOR UNIT
CONTROL
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
AIR FLOW CFM 1060 870 680 510
NOMINAL WATER FLOW RATE
USGPM 9.00 7.43 6.01 4.71
litres/min 34.06 28.12 22.76 17.83
HEAD LOSS (COOLING) kPa 41 30 22 15
HEAD LOSS (HEATING) : 50°C kPa 37 26 20 12
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.08 0.89 0.70 0.52
SOUND PRESSURE LEVEL dBA 51 46 41 34
UNIT DIMENSION - (WITH PANEL) H X W X D mm 300 x 820 x 820 (375 x 990 x 990)
PACKING DIMENSION - (PANEL) H X W X D mm 376 x 916 x 916 (125 x 1020 x 1020)
UNIT WEIGHT (UNIT + PANEL) kg 32 + 4
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
FAN
TYPE TURBO FAN
DRIVE DIRECT
FAN SPEED RPM 750 630 510 400
FAN EFFICIENCY % 55.6 55.5 49.6 49.4
FAN MOTOR
TYPE BRUSHLESS DIRECT CURRENT
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE E
RATED RUNNING CURRENT A 0.95 0.55 0.35 0.21
STARTING CURRENT A N/A
MOTOR OUTPUT W 100
MOTOR EFFICIENCY % 75.0 75.0 75.0 75.0
POLES 8
COIL
TUBE
MATERIAL COPPER
DIAMETER mm 7.00
FIN
MATERIAL ALUMINIUM
FACE AREA m
2
0.46
ROW 3
WATER VOLUME litre 2.35
AIR QUALITY FILTER
TYPE WASHABLE SARANET FILTER
QUANTITY pc 1
CASING COLOUR WHITE
NOTE:
A) BASED ON EUROVENT CONDITIONS
B) ADDITIONAL 10W IS REQUIRED FOR CONDENSATE DRAIN PUMP
C) SOUND PRESSURE LEVEL IS TESTED AS PER JIS STANDARD AS BELOW:
FWKE05E(H) MODEL - 1.4M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
FWKE08/11E(H) MODEL - 1.5M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
MODE COOLING HEATING
ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
ENTERING WATER TEMPERATURE 7°C
50°C (2 Pipes System)
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.