32
Sound Data
Model Speed
1/1 Octave Sound Power Level (dB, reference 1pW)
Overall
(dBA)
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
FWKE05E(H)
High 49 50 45 36 26 20 19 46
Med
46 44 39 28 16 15 18 40
Low 38 40 32 22 14 15 20 34
Quiet 33 38 24 15 10 14 18 30
FWKE08E(H)
High 59 58 56 50 42 42 30 67
Med
54 54 51 44 37 34 23 52
Low 57 55 45 37 29 22 25 49
Quiet 50 44 39 29 17 15 19 40
FWKE11E(H)
High 63 60 58 53 45 46 34 59
Med
60 55 54 48 40 40 27 55
Low 58 50 49 41 34 29 20 49
Quiet 53 45 42 33 22 16 19 43
Measured In Reverberation Chamber
Model Speed
1/1 Octave Sound Power Level (dB, reference 1pW)
Overall
(dBA)
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
FWE05E
High 51 58 55 52 47 41 35 62
Med
47 52 49 45 39 32 27 55
Low 44 50 47 42 36 28 29 53
FWE06E
High 54 60 58 55 50 44 38 63
Med
50 55 54 50 45 38 30 59
Low 47 52 20 45 40 32 23 56
FWE07E
High 55 61 59 57 52 46 41 66
Med
52 59 56 53 48 42 35 62
Low 48 54 52 48 42 35 28 58
FWE08E
High 62 65 60 59 55 50 43 64
Med
58 63 57 57 52 46 39 61
Low 56 60 54 54 48 42 34 58
FWE10E
High 65 66 61 60 56 50 44 65
Med
59 63 58 57 51 45 39 61
Low 57 60 55 54 48 41 34 58
FWE12E
High 61 66 61 61 56 52 45 65
Med
60 64 60 58 54 48 41 63
Low 57 63 57 56 51 45 40 61
Measured In Reverberation Chamber