34
Sound Data
Model Speed
1/1 Octave Sound Power Level (dB, reference 1pW)
Overall
(dBA)
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
FWC02FD
High 56 59 59 55 50 45 38 61
Med 57 58 58 54 49 44 37 60
Low 54 54 54 50 44 38 31 56
FWC03FD
High 59 61 60 57 55 50 42 63
Med 59 61 59 56 53 48 40 62
Low 58 59 58 54 51 45 38 60
FWC04FD
High 59 61 61 58 54 49 42 64
Med 60 60 60 57 53 48 41 63
Low 60 56 56 53 49 42 34 59
FWC05FD
High 61 62 63 60 57 52 46 66
Med 60 62 62 60 57 52 45 66
Low 57 58 59 57 53 47 39 62
FWC06FD
High 63 65 65 62 56 51 46 67
Med 62 64 64 61 55 51 45 66
Low 58 60 61 57 51 46 39 63
FWC08FD
High 66 66 65 62 58 53 47 68
Med 67 65 64 61 57 52 47 67
Low 64 65 63 60 55 49 44 65
FWC10FD
High 66 67 67 64 61 56 50 70
Med 65 66 67 64 60 55 49 69
Low 63 64 64 62 57 52 46 67
Measured In Reverberation Chamber
Model
(LSP)
Speed
1/1 Octave Sound Power Level (dB, reference 1pW)
Overall
(dBA)
125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
FWC02G
High
61 52 54 54 47 41 32 57
Med 53 49 51 50 42 35 29 53
Low 47 45 46 44 35 26 21 47
FWC03G
High 56 55 57 57 51 47 37 60
Med 55 51 52 51 45 39 28 55
Low
49 43 44 41 33 24 23 45
FWC04G
High 58 58 59 59 54 49 40 62
Med 55 55 56 55 49 43 33 58
Low 47 47 47 44 37 28 21 48
FWC06G
High
60 60 60 59 54 51 44 63
Med 59 58 58 57 52 48 40 61
Low 54 54 54 53 46 42 33 56
FWC08G
High 60 60 60 58 53 49 41 62
Med 57 56 56 55 48 43 34 58
Low 50 50 50 47 39 32 25 51
FWC10G
High 62 62 62 61 57 53 46 65
Med 59 59 60 59 53 48 41 62
Low 54 54 55 54 47 41 31 57
FWC12G
High 64 62 62 61 56 52 44 65
Med 61 60 60 58 52 48 40 62
Low
58 56 57 54 48 42 33 58
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).