100 Design Guide DCM014A51
Continued from previous page
Before (BACnetGW
(Ver6.34.00))
After (iTM for North
America)
Analog Input
(Room
Temperature)
IN_ALARM (TRUE: Analog
maximum/minimum error)
FAULT (TRUE: Communication
error or Sensor error)
FAULT (TRUE:
Communication error or
Sensor error)
OVERRIDDEN (Always FALSE)
OVERRIDDEN (Always
FALSE)
OUT_OF_SERVICE (Always
FALSE)
OUT_OF_SERVICE (Always
FALSE)
FAULT: Communication
error/Sensor error
LOW_LIMIT: Analog minimum
error
HIGH_LIMIT: Analog maximum
error
Analog Value
(Occ Cooling
Setpoint, Occ
Heating Setpoint,
Unocc Cooling
Setpoint, Unocc
Heating Setpoint,
Max Cooling
Setpoint, Min
Cooling Setpoint,
Max Heating
Setpoint, Min
Heating Setpoint,
Min Setpoint
Differential
(Cooling &
Heating))
["Unocc Cooling Setpoint“,
"Unocc Heating Setpoint",
"Max Cooling Setpoint“,
"Min Cooling Setpoint",
"Max Setpoint“, "Min
Setpoint"]
TRUE: Disabled
FALSE: Enabled
[Other]
Always FALSE