Continued from previous page
100 Design Guide DCM014A51
Continued from previous page
Object Type
Property Identifier
Before (BACnetGW
(Ver6.34.00))
After (iTM for North
America)
Property
Analog Input
(Room
Temperature)
Status_Flags
IN_ALARM (TRUE: Analog
maximum/minimum error)
IN_ALARM (Always FALSE)
FAULT (TRUE: Communication
error or Sensor error)
FAULT (TRUE:
Communication error or
Sensor error)
OVERRIDDEN (Always FALSE)
OVERRIDDEN (Always
FALSE)
OUT_OF_SERVICE (Always
FALSE)
OUT_OF_SERVICE (Always
FALSE)
Event_State
NORMAL: Normal
Fixed to NORMAL
FAULT: Communication
error/Sensor error
LOW_LIMIT: Analog minimum
error
HIGH_LIMIT: Analog maximum
error
Analog Value
(Occ Cooling
Setpoint, Occ
Heating Setpoint,
Unocc Cooling
Setpoint, Unocc
Heating Setpoint,
Max Cooling
Setpoint, Min
Cooling Setpoint,
Max Heating
Setpoint, Min
Heating Setpoint,
Min Setpoint
Differential
(Cooling &
Heating))
Out_Of_Service
Always FALSE
["Unocc Cooling Setpoint“,
"Unocc Heating Setpoint",
"Max Cooling Setpoint“,
"Min Cooling Setpoint",
"Max Setpoint“, "Min
Setpoint"]
TRUE: Disabled
FALSE: Enabled
[Other]
Always FALSE